1.5mm2 To 1000mm2 Steel Tape Armored Cable WDZ-YJY23 LSZH XLPE
Product Summary
Product Details
Product Description
WDZ-YJY23 is a low-smoke halogen-free (LSZH) sheathed, cross-linked polyethylene (XLPE) insulated, and steel-tape armored low-voltage power cable designed for fixed installations with complex routing and clearly defined safety requirements. It is suitable for underground and protected distribution lines requiring additional resistance to external stresses, while reducing smoke emissions and the generation of corrosive halogen gases in the event of a fire. For contractors and engineering, procurement, and construction (EPC) contractors, WDZ-YJY23 is a practical choice, meeting the needs for line durability and enhanced fire resistance in enclosed or building connections.
Typical Low Voltage Rating: 0.6/1kV
Applications: Building feeders, industrial park power distribution, industrial low-voltage trunk and branch lines (fixed installation)
- Incoming lines from transformer areas to main low-voltage switchboards, with routes including buried or protected channels.
- Underground conduits and piping systems in industrial parks, commercial complexes, and residential developments.
- Protected trench routes, considering backfill pressure and long-term external loads.
- Cable ducts, service corridors, and utility corridors, with safety management requirements conforming to Low Smoke Halogen-Free (LSZH) standards.
- Low-voltage distribution lines in public utilities, where path protection and safety clauses are clearly specified in procurement documents.
- Mobile equipment, dragging, frequent bending, or flexible dragging services.
- High-impact areas where additional mechanical protection requirements are not confirmed.
- 1C for high-current feeders and phase-separated cabling
- 2C for dedicated single-phase feeders and auxiliary power supplies
- 3C For three-phase circuits without a neutral conductor (depending on specific design)
- 4C for three-phase distribution with a neutral conductor
- 5C for three-phase distribution with a neutral conductor and protective grounding (depending on specific design)
- 3+1 and 3+2 for feeder arrangements used in many Bills of Quantities (BOQs)
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400
- 4C x 25 4C x 35 4C x 50
- 5C x 16 5C x 25 5C x 35
- 3C x 16 3C x 25
- 1C x 150 1C x 185 1C x 240
Adapted to local design specifications 3+1 and 3+2 Constructions
Note: Final construction details depend on the required standards, conductor class, and Low Smoke Halogen-Free (LSZH) composite system.
Choosing an LSZH sheath system reduces smoke concentration, limits the release of halogen-related corrosive gases, thereby improving visibility and reducing the risk of secondary damage to equipment in enclosed or building-connected wiring.
Choosing steel tape armor enhances the cable's compression resistance and external stress resistance, which is particularly important for protected underground wiring, trench wiring, and congested utility corridors.
The insulation layer is extruded and cross-linked to form a robust dielectric layer suitable for low-voltage distribution applications.
Core marking and strand length are controlled to maintain roundness, resulting in a smoother sheath and more stable traction performance.
Side layers are applied to protect the core assembly and provide a stable base for steel tape winding.
Steel tape is wound in a controlled overlap pattern, primarily providing mechanical reinforcement against compression and external stress.
A low smoke halogen-free sheath is extruded to protect the armor layer and meet the project's low smoke halogen-free performance requirements.
Typical inspections include conductor resistance, insulation thickness verification, spark testing, voltage testing, dimensional control, and sheath integrity checks. All compliance checks meet specified standards.
| Product Model | WDZ-YJY23 |
|---|---|
| Cable Type | Low-smoke halogen-free cross-linked polyethylene (XLPE) copper core power cable, steel tape armor |
| Rated Voltage | 0.6/1kV |
| Conductor | Copper, stranded wire |
| Insulation | Cross-linked polyethylene (XLPE) |
| Armor | Steel tape |
| Outer Sheath | Low-smoke halogen-free (LSZH) |
| Common Core Wire Specifications | 1 core, 2 cores, 3 cores, 4 cores, 5 cores, 3+1 cores, 3+2 cores |
| Common Wire Diameter Range | 1.5 to 400 mm² |
| Typical operating temperature | Up to 90°C (XLPE design, depending on standard) |
| Installation methods | Conduit, underground protected wiring, protected trenches, cable trays, maintenance access |
| Packaging | Export reels, reel lengths customizable |
| Optional services | Custom marking, packaging marking, document kits, reel scheduling plans |
- Confirm the wording of the Low Smoke Halogen-Free (LSZH) requirements in the Bill of Quantities. (BOQ)
- Select conductor configuration based on neutral and protective grounding design.
- Select cross-sectional area based on load current, line length, environmental conditions, grouping method, and allowable voltage drop.
- Clearly define the installation path (conduit, protective trench, utility access, inlet).
- Specify reel length preference to reduce joints and speed up installation.
- If the environment involves water, chemicals, or special mechanical risks, declare this in the Request for Quotation (RFQ) to select appropriate sheathing and protection solutions.
Cable Type: WDZ-YJY23
Voltage: 0.6/1kV
Conductor Configuration: __
Size and Quantity: __
Total Length: __ meters
Installation Path: __
Required Standards and Classifications: __
Destination Country and Port: __
Trade Terms: __
Preferred Reel Length: __
Required Documents: __
Remarks: Low Smoke Halogen-Free (LSZH) Markup language and delivery schedule required
-
How does WDZ-YJY23 differ from standard Low Smoke Halogen-Free (LSZH) power cable?
It features added steel tape armor, providing better resistance to external pressure and installation stress, making it more suitable for protected underground lines and incoming lines.
-
What does "23" in the name mean?
In many naming systems, "23" is associated with a steel tape armor construction. The specific definition must follow the standards specified in the project documentation.
-
Is WDZ-YJY23 suitable for flexible or mobile equipment?
No. It is designed for fixed installations. For equipment that is frequently moved, choose a flexible cable designed for dynamic applications.
-
Can it be used for direct burial?
It is typically used for protected underground lines. The suitability for direct burial depends on local regulations, soil conditions, and mechanical risks. Please provide line details for proper selection.
-
What is the most commonly used specification in projects?
Multi-core 4-core and 5-core cables ranging from 16 to 50 mm² are widely used in power distribution; high-current feeders typically use single-core cables ranging from 120 to 240 mm², depending on the load and distance.
-
What information is needed for an accurate quote?
Standard requirements, conductor configuration, size list, total length, route type, destination, reel preference, and required documentation.
JinHong has a wide range of cable and conductor products for you to choose from. We will provide caring services and professional project solutions for everyone who needs them.
JinHong cable products are manufactured according to GB, IEC, BS, NFC, ASTM, DIN, and other international standards. Our technical team can customize cable products that meet your requirements according to your needs.
JinHong provides free professional consulting services to provide you with one-stop project solution services and rapid product delivery solutions.
While we at JinHong provide high-quality cables, we also provide good delivery solutions. While ensuring the safe delivery of products, we provide the best packaging and transportation solutions, greatly reducing customers’ transportation costs.
JinHong cable packaging is provided in the form of wooden reels, corrugated boxes, and coils. The cable ends are sealed with BOPP self-adhesive tape and a non-hygroscopic sealing cap to protect the cable ends from moisture. We can print the required marks on the outside of the barrel with waterproof material according to customer requirements.